printPrint
  1. pin-int

Service Track® TK-ST160-3Y208-N

TK-ST160-3Y208-N Surge Protection Device, 120/208 VAC, 40 to 440 Hz, 200 kA SCCR, 3 ph Phase

  • MPN: TK-ST160-3Y208-N
  • Min. Order Qty: 1
  • Quantity Interval: 1
  • loading loading
Service Track® TK-ST160-3Y208-N

Service Track® Surge Protection Device, 120/208 VAC Electrical Rating, 40 to 440 Hz Frequency, 4 Wires, 200 kA Short Circuit, 160 kA/ph/80 kA/Mode Peak Surge Current, Modes of Protection: L-N/L-G/L-L/N-G, <1 ns Response, LED Indicator, 3 ph, Environmental Conditions: 5 to 95% Non-Condensing Relative Humidity, NEMA 4/IP56 Enclosure, Multi-Point Feet Mounting, 11.5 in H x 8.28 in W x 6.28 in D Dimensions

Dimensions      :      11.5 in H x 8.28 in W x 6.28 in D
Electrical Ratings      :      120/208 VAC
Enclosure Type      :      NEMA 4/IP56
Environmental Conditions      :      5 to 95% Non-Condensing Relative Humidity
Frequency Rating      :      40 to 440 Hz
Indicator Type      :      LED
Modes of Protection      :      L-N/L-G/L-L/N-G
Mounting Type      :      Multi-Point Feet
Number of Wires      :      4
Peak Surge Current      :      160 kA/Phase/80 kA/Mode
Response Time      :      <1 ns
Short Circuit Current Rating      :      200 kA
  • Providing the highest level of protection with the lowest let-through voltage in the industry
  • Fail-safe design
  • Optional component-level fusing
  • Single pulse tested at independent third party lab
  • Form C dry relay contacts and audible alarm with silence button
  • Two suppression technologies - MOV and all mode enhanced transient filter
  • Ultra, compact footprint - efficiency and performance
  • 4-wire plus ground
  • Optimum performing parallel hybrid with component-level fusing design
  • Status indicator lights (one per phase & one service LED)
  • Form C dry relay contacts for suppressor status
  • Audible alarm with silence button
  • Hard-wired via internal lugs connection method
  • #10 to 2 AWG wire size
  • 150 V for L-N/L-G/N-G, 300 V for L-L MCOV
  • 40 V at L-N mode/76 V at L-G mode/46 V at L-L mode/54 V at N-G mode, A1 ring wave/2 kV/87 A/180 deg phase angle
  • 651 V at L-N mode/640 V at L-G mode/1041 V at L-L mode/646 V at N-G mode, B3/C1 impulse wave/6 kV/3 kA/90 deg phase angle
  • 960 V at L-N mode/1010 V at L-G mode/1310 V at L-L mode/860 at N-G mode, C3 impulse wave/20 kV/10 kA/90 deg phase angle
  • 400/700 V at L-N mode/L-G mode/N-G mode, 800/1200 V at L-L mode UL 1449 voltage protection ratings
  • -40 to 160 deg F operating temperature
  • pdfSpecification Sheet https://assets.unilogcorp.com/2/ITEM/DOC/TPS_TK_ST160_3Y208_N_Datasheet.pdf