HPS Centurion® H1EM300PB00 Energy Efficient Harmonic Mitigating Transformer, 600 Delta VAC Primary, 208Y/120 VAC Secondary, 300 kVA Power Rating, 60 Hz, 3 Phase
Sold as: Pack of 1/PK
HPS Centurion® energy efficient harmonic mitigating distribution transformers are rated for 600 VAC and below. Typical applications of severe non-linear loading conditions include data centers, internet service providers, telecom sites, call centers, broadcast centers, etc. Energy efficient harmonic mitigating transformers with zero sequence flux cancellation technology, is specifically designed to treat the harmonics generated by computer equipment and other non-linear, power electronic loads. Superior to K-rated and conventional transformers in reducing voltage distortion (flat topping) and power losses due to current harmonics created by 1-phase, non-linear loads such as computer equipment. Combining zero sequence flux cancellation with phase shifting treats 3rd, 5th, 7th, 9th, 15th, 17th and 19th, harmonics within its secondary windings.
HPS Centurion® Harmonic Mitigating Transformer, Energy Efficient, 600 Delta VAC Primary, 208Y/120 VAC Secondary, 300 kVA Power, 60 Hz Frequency, 3 ph, 0 deg Zigzag/Lug/Pad Connection, Floor Mounting, 220 deg C Insulation, NEMA 3R Enclosure, 30 to 40 deg C, 98.59 % Efficiency, 38 in L x 48-1/2 in W x 59 in H Dimensions
Connection Type | : | 0 deg Zigzag/Lug/Pad |
Dimensions | : | 38 in L x 48-1/2 in W x 59 in H |
Efficiency | : | 98.59 % |
Enclosure Type | : | NEMA 3R |
Insulation | : | 220 deg C |
Mounting Type | : | Floor |
Temperature Rating | : | 30 to 40 deg C |
Type | : | Energy Efficient |
Primary Voltage | : | 600 Delta VAC |
Secondary Voltage | : | 208Y/120 VAC |
Power Rating | : | 300 kVA |
Frequency Rating | : | 60 Hz |
Phase | : | 3 |